38 Display Operation Manual BC2000 and JC2000 Controller ~ Doc. No. 2055882, Issue 5.1, June 2014
Parameter Description
Default
Setting
Value Range
Activate
Manual BDT
(Executable)
Activates the battery discharge test if
enabled under the “Battery Mgt” menu.
NA NA
Manual Boost
(Executable)
Activates battery boost if enabled under the
“Battery Mgt” menu.
NA NA
Test Mode
Enables or disables the relay test function,
which permits controller output relays to be
activated
Disabled
Disabled /
Enabled
Relay (A-F)
Activates a single controller output relay.
Test Mode must be enabled.
Inactive
Inactive /
Active
Lamptest
(Executable)
Temporarily illuminates all LEDs (controller,
display, rectifiers, etc)
NA NA
Battery Mgt
BDT State
Enables or disables the battery discharge
test feature. If enabled, “Manual BDT”
appears under the “Activate” menu.
Disabled
Disabled /
Enabled
BDT Duration
The length of time that the battery discharge
test is scheduled to run
00:30:00
(HH:MM:SS)
Max 17:59:59
BDT Alarm V
An alarm is triggered if the battery terminal
voltage falls below this value during the
battery discharge test
52 V
44 – 53 V
(Min: BDT
abort +1 to -1)
BDT Abort V
If the battery terminal voltage falls below this
value during the battery discharge test, the
battery discharge test is aborted and an
alarm is triggered. This value should be at
least 2V below BDT Alarm V
43 V
43 – 52 V
(Min: LVD
Disconnect V +
1V,
Max: BDT
Alarm V. 1V)
BDT Alarm
Delay
The time in minutes the controller waits after
the test has dropped below the BDT Alarm V
to trigger the alarm
15 mins 0 – 30 mins
BDT Auto
Mode
Enables the automatic BDT Start Mode Disabled
Disabled /
Enabled
Boost State
Enables or disables the battery boost /
equalize function
Disabled
Disabled /
Enabled
Boost
Duration
Duration of time the equalize / boost is active
12:00:00
(HH:MM:SS)
Max
255:59:59
Boost Voltage
The voltage to which the equalize / boost
charge increases
56.5 V 55 – 57 V
Boost Stop
Current
Stops the boost mode if the current value has
gone below this set point
0A 0 – 255 A
Generator*
State Enables or disables the generator feature Disabled
Disabled /
Enabled
Type
Select the type of generator in use (either air-
cooled or “other”)
Other
Air Cooled /
Other