Display Operation Manual BC2000 and JC2000 Controller ~ Doc. No. 2055882, Issue 5.1, June 2014 39
Parameter Description
Default
Setting
Value Range
Battery AH
Set the ampere-hour rating of the battery
string supported by the generator
370 AH 20 – 1000 AH
Thermal
Internal Min
When internal temperature falls below this
value, the Temperature Alarm (Minor) is
cleared
93°C
-40 – 93°C
(-40 – 199°F)
Internal Max
When internal temperature exceeds this
value, the Temperature Alarm (Minor) is
issued
98°C
98 – 120°C
(208 – 248°F)
External Min*
When external temperature falls below this
value, the Temperature Alarm (Minor) is
cleared
93°C
-40 – 93°C
(-40 – 199°F)
External Max*
When external temperature exceeds this
value, the Temperature Alarm (Minor) is
issued
98°C
98 – 120°C
(208 – 248°F)
T Comp Status Enables or disables thermal compensation Disabled
Disabled /
Enabled
T Comp Sense
Selects either the internal sensor or an
external temp probe as the sensing device for
battery temperature compensation
External
Internal /
External
T Comp Boost
Adjust
Activates battery boost during temperature
compensation
Disabled
Disabled /
Enabled
High T Start
The controller begins reducing the float
voltage when the highest measured battery
temperature reaches this value
35°C
25 – 60 °C
(77 – 140°F)
High Slope
If battery temperature exceeds the High T
Start value, the controller linearly reduces the
plant voltage by this slope
72 mV/°C 0 – 250 mV/°C
High V Stop
The minimum voltage to which the controller
reduces plant voltage for thermal
compensation
50.5 V
48 – 57 V
(max HVSD –
1V)
Low T Start
The controller begins increasing the float
voltage when the lowest measured battery
temperature reaches this value
-20°C
-20 – 25 °C
(-4 – 77°F)
Low Slope
If battery temperature is below the Low T
Start, the controller linearly increases the
plant voltage by this slope
0 mV/°C 0 – 250 mV/°C
Low V Stop
The maximum voltage to which the controller
raises plant voltage for thermal
compensation
56 V
48 – 57 V
(max HVSD –
1V)
Runaway
Temp
The temperature at which the controller
reduces the Float Voltage to Thermal
Runaway Clamp Voltage (Runaway V)
60°C
45 – 70 °C
(113 – 158°F)
Runaway V
The voltage to which the controller reduces
while temperature is above the Runaway
Temperature value
50 V 45 – 50 V