EasyManua.ls Logo

Emerson AMS Trex - Appendix A Troubleshooting; Troubleshoot HART Communication

Emerson AMS Trex
214 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A
Troubleshooting
Topics covered in this appendix:
Troubleshoot HART communication
Troubleshoot fieldbus communication
A.1 Troubleshoot HART communication
Symptom Possible cause Solution
"No Voltage Detected"
message is displayed.
The lead set is improperly
connected to the device.
Attach the lead set to the
device.
The Trex unit is connected to a
4-wire device or a wireless
device that is powered by its
battery.
None. This is expected
behavior.
There is intermittent
communication.
Insufficient loop current and
voltage at the device terminals.
Verify there is at least 4 mA and
12 VDC at the device terminals.
Noise on the loop, or noise or
signal distortion from the
control system. For example,
noise from the power supply
powering the devices, or front
end analog circuitry inside the
control system may be
distorting the HART signal.
An oscilloscope can help
determine noise or signal
distortion of HART signals.
Poor wiring. Check the wiring terminations
and exposed signal wire for
damage.
There is no communication
with device.
Insufficient loop resistance at
the HART frequencies.
Add an additional 250 ohm
resistor in series in the loop.
Place the leads across the
resistor and verify
communication occurs.
Insufficient loop current and
voltage at the device terminals.
Verify there is at least 4 mA and
12 VDC at the device terminals.
The AC adapter is attached to
the Trex unit.
Remove the AC adapter from
the Trex unit and try to connect
to the device.
Troubleshooting
User Guide 179

Table of Contents

Other manuals for Emerson AMS Trex

Related product manuals