Device connection wizard prompts Answer
Do you intend to provide power from the
Trex unit?
Yes
Are you providing power to a transmitter or
positioner?
Positioner
Change Polling Option? Tap Yes if the device is not at address zero.
Increase loop current? Tap Yes to increase the current from 4 mA to
another value, if the device did not initially
communicate.
Connect to an externally-powered HART positionerFigure 3-17:
A. Current source
Device connection wizard prompts Answer
Do you intend to provide power from the
Trex unit?
No
Leads are attached to: Positioner
Change Polling Option? Tap Yes if the device is not at address zero.
Increase loop current? Tap Yes to increase the current from 4 mA to another
value, if the device did not initially communicate.
Related information
HART communication terminals
Connect to an externally-powered HART device
Power and connect to a HART device
Internal resistors
Field Communicator application