Installation
29 Liebert
®
APS
Configuring the Bypass Voltage
The UPS bypass voltage is factory-set to 208V (the jumper copper bar has been installed). Should the
user have a utility supply of 200V/220V/230V/240V, the bypass voltage jumper must be changed to
ensure correct output voltages when in bypass mode. Configuring the bypass voltage jumper settings
are shown in Figures 34 and 35. Refer to Table 7 for the proper setting according to the AC mains
voltage configuration.
Figure 34 Setting bypass voltage jumper (default: 208VAC)
Figure 35 Setting bypass voltage jumper (200/220/230/240VAC)