Emerson Liebert APS - Table 26 Rated Input Voltage Range (Unit: VAC)

Emerson Liebert APS
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
Liebert
®
APS
70
Battery Module
Lead-Acid Batteries
Per String, Pieces
12
Battery Cells Per String,
Pieces
72
Battery Capacity, W 36W @ 15min-rate to 1.67V per cell @25°C (77°F)
Backup Time, Minutes,
Full Load 5 (for non-redundant system which has equal number of battery strings and power modules)
Maximum Charge Current
(Full, Load)
Power module internal charger: 1.8A
Charger module: 10A
Nominal Voltage, VDC 144
Recharge Time, Hr < 5 to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
Output data
Output Voltage, VAC
200/208/220/230/240
Single-Phase
100/100/173/200
110/110/190/220
115/115/199/230
120/120/208/240
Single-Phase
200/100, 208/120, 220/110
230/115, 240/120
Single-Phase
Voltage Regulation, % ±3
Voltage Stability
(100% Step Load), %
±7
Voltage Recovery Time, ms 60
Voltage Distortion, %
3, linear load
5, non-linear load 7, non-linear load 5, non-linear load
Output Frequency, Hz 50/60
Output Overload
Capability, %
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec
Table 26 Rated input voltage range (Unit: VAC)
% UPS Load Low Limit Value High Limit Value
> 100% load 170 ±5
280 ±5
90 ~ 100% load 160 ±5 ~ 170 ±5
70 ~ 90% load 140 ±5 ~ 160 ±5
50 ~ 70% load 120 ±5 ~ 140 ±5
< 50% load 120 ±5
Table 25 Liebert APS specifications (continued)
Unit Size, Type
10 Bay 16 Bay 12 Bay 16 Bay 10 Bay 16 Bay
No Transformer Transformer-based
No Transformer
Dual Inverter
Frame Rating, kVA/kW 15/13.5 20/18 15/13.5 20/18 15/13.5 20/18