Specifications
71 Liebert
®
APS
™
Table 27 Specifications of Liebert APS external battery cabinet
Parameters AS7EBCNCC1BX000
General and Environmental
Conducted and Radiated EMC Levels IEC/EN/AS 62040-2—Class A, FCC Part 15 (Class A)
Safety Standards IEC/EN/AS 62040-1:2008, UL 1778 4th Ed and CSA 22.2 No. 107.3
Immunity Standards IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation ISTA-1E
Dimensions, WxDxH
17x28x38
(440x712x970)
Unit Weight, lb (kg) 147.7 (67)
Shipping Weight, lb (kg) 209.4 (95)
Environmental
Operating Temperature °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C)
Without battery: -4 to 140 (-20 to 60)
With battery: 5 to 104 (-15 to 40)
Relative Humidity, % 0 - 95%, non-condensing
Altitude, ft. (m) 10000 (3000)
Battery Module *
Lead-Acid Batteries (Per String) 12
Backup Time (Full Load), Minutes See Estimated Battery Run Times, 7.1 through 7.5
* Up to four external battery cabinets can be connected to each UPS frame and each external battery cabinet can be configured
with up to seven strings of batteries.