Specifications
69 Liebert
®
APS
™
7.0 SPECIFICATIONS
Table 25 Liebert APS specifications
Unit Size, Type
10 Bay 16 Bay 12 Bay 16 Bay 10 Bay 16 Bay
No Transformer Transformer-based
No Transformer
Dual Inverter
Frame Rating, kVA/kW 15/13.5 20/18 15/13.5 20/18 15/13.5 20/18
General & Environmental
Conducted and Radiated
EMC Levels
IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
Compliant Safety Standards
IEC/EN/AS 62040-1:2008,
UL 1778 4
th
Ed and CSA 22.2 No. 107.1
UL 1778 4
th
Ed and
CSA 22.2 No. 107.1
Compliant Immunity
Standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation Individual packaged modules meet ISTA-1A / 1B; the complete system meets ISTA-1E
UPS Classification According
to IEC EN 62040-3
VFI-SS-111
Environmental WEEE and ROHS2 (6 by 6), REACH Compliant
Protection Degree
IEC60529
IP 20
Color RAL 7021
Dimensions, W x D x H, mm (in)
440 x 800 x 695
(17x32x27)
440x850x970
(17x34x38)
440x800x1060
(17x32x42)
440x850x1240
(17x34x49)
440x800x695
(17x32x27)
440x850x970
(17x34x38)
Weight, kg (lb)
Unit Weight
(empty frame)
127 (280) 145.1 (320) 231.3 (510) 244.9 (540) 127 (280) 145.1 (320)
Shipping Weight
(empty frame)
145.1 (320) 163.3 (360) 249.5 (550) 263.1 (580) 145.1 (320) 163.3 (360)
Unit Weight
(frame rating populated)
256.3 (565) 317.5 (700) 360.6 (795) 417.3 (920) 256.3 (565) 317.5 (700)
Shipping Weight
(frame rating populated)
274.4 (605) 335.7 (740) 378.7 (835) 435.4 (960) 274.4 (605) 335.7 (740)
Environmental
Operating Temperature,
°C (°F)
0 - 40 (32 - 104)
Relative Humidity, % 0 - 95%, non-condensing
Altitude, m (ft) 3000 (10000) @ 25°C (77°F)
Efficiency (AC-AC), % 91.8-92.0 91.6-92.0 88.5-89.9 88.6-89.7 90.4-91.0 90.0-91.0
Nominal Heat Dissipation
BTU/Hr (maximum)
4208 5747 5528 7965 4904 6768
Acoustic Noise Level, dBA < 55dB (<
50% load), < 65dB (51-100% load) @ 1 meter
Input data
Nominal Input Voltage,
VAC
200/208/220/230/240; Single-Phase 200/100, 208/120, 220/110,
230/115, 240/120;
Single-Phase
380/400/415; Three-Phase — —
Input Voltage Range,
VAC
The input voltage range based on the output loading, refer to Table 26
Power Factor, Cos
Single-Phase Input, >
0.99;
Three-phase Input, >
0.95
Single-Phase Input, >
0.99
Input Frequency, Nominal,
Hz
50/60
Input Current
Distortion, THDi
< 5%
Input Frequency Range, Hz 40 to 70 auto-sensing