Operation and Display Panel
51 Liebert
®
APS
™
4.3.2 Battery Screen
From the main screen, press the F3 button once and the battery screen will be displayed, as shown in
Figure 57.
Figure 57 Battery screens
On the first battery screen, pressing the F5 button will change the function of the F2, F3, and F4
buttons from the primary functions to the secondary functions, as shown above in Table 21.
The battery screen displays Battery voltage, Battery current, Battery time remaining, Battery
capacity, Battery state, Battery string count, Battery temperature, cumulative discharge count
(highest of all installed battery modules), cumulative discharge time (in hours) and External battery
cabinet count.
4.3.3 Output Screen
The main screen is the output screen by default, as shown in Figure 58.
Figure 58 Output screen
The output screen displays L-N or L-L voltage, L-N or L-L current, Frequency and Power factor.
Battery
Liebert APS
2014-01-01
10:45:20
▲
▲
▲
Batt temp (°C)
Discharge count
Discharge hour (H)
Ext batt -cab count
25.0
303
9.4
0
Battery
Liebert APS
2014-01-01
10:45:20
▲
▲
▲
Batt voltage (V)
Batt current (A)
Remain time (Min
Batt capacity (%)
Batt state
Batt string count
157.0
0.03
407
100
Fully Charged
0
First Screen Second Screen