49
Changing the Sensor Conguration between Normally Open & Normally Closed
To change the Lighting signal between Normally Open or Normally closed:
Turn thermostat ON;
Press & hold the CONFIG button for 5 seconds, the screen will show 0011;
Press CONFIG button, the screen will show CCC;
Press the F/C button three (3) times;
Press the UP / DOWN button to set the setting to 1;
Press the FAN button to switch the control value to the O / C.;
Press Up / Down button to set the value to O/C;
O – Energized when room is empty
C – Energized when room is Occupied
Press the OFF button to save the settings.
Press the RESET button on the front of thermostat.