EAOM-210 FLJ.eng / ver 0.0
Pages 115 / 132
10- Miscellaneous Page:
DATE: 30 02 2009
TIME: 14
WORKING HOUR : 1
NEXT MAINT.HOUR
/ /
:20:58
:5000
NEXT MAINT.MONT: 6
RUN: 7 START: 11
AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!
DATE - Real Date: Day, Month, Year.
TIME - Real Time: Hour, minute, second.
WORKING HOUR – Engine run time
NEXT MAINT.HOUR - The remaining hour for maintenance
NEXT MAINT.MONT - The remaining month for maintenance
RUN – Number of generator runs
START - Number of generator starts
11- J1939 Values Page:
J1939 VALUES
ENGINE SPEED
TEMPERATURE : 27ºC
WORKING HOUR:000002h
SPN: 91 FMI: 3
:1500Rpm
OIL PRESSURE: 4.0Bar
AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!
ENGINE SPEED – Engine speed via J1939
OIL PRESSURE – Oil pressure via J1939
TEMPERATURE – Coolant temperature via J1939
WORKING HOUR – Working hour via J1939
SPN – Suspect parameter number (Active Faults DM1 via J1939)
FMI – Failure mode identifier (Active Faults DM1 via J1939)
12- J1939 SPN & FMI Page:
SPN1: 0
FMI1: 0 OC1: 0
AUTO CRANKNG ATTEMP
OVER SPEED PREALARM!
SPN2: 0
FMI2: 0 OC2: 0
SPN3: 0
FMI4: 0 OC3: 0
SPN1 – Suspect parameter number-1 (Active Faults DM1 with the Multipacket
Transport via J1939)