Deltabar PMD78B PROFINET with Ethernet-APL Mounting
Endress+Hauser 23
5.2.3 Oxygen applications (gaseous)
Oxygen and other gases can react explosively to oils, grease and plastics. The following
precautions must be taken:
All components of the system, such as devices, must be cleaned in accordance with the
national requirements.
Depending on the materials used, a certain maximum temperature and a maximum
pressure must not be exceeded for oxygen applications.
The cleaning of the device (not accessories) is offered as an optional service.
p
max
: PN of flange, max. 80 bar (1 200 psi)
T
max
: 60 °C (140 °F)
5.2.4 Thermal insulation when mounting with a temperature
isolator
The device may only be insulated up to a certain height. The maximum permitted
insulation height applies to an insulation material with a thermal conductivity ≤ 0.04 W/
(m x K) and to the maximum permitted ambient temperature and process temperature.
The data were determined under the application "quiescent air".

Table of Contents

Other manuals for Endress+Hauser Deltabar PMD78B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Endress+Hauser Deltabar PMD78B and is the answer not in the manual?

Endress+Hauser Deltabar PMD78B Specifications

General IconGeneral
BrandEndress+Hauser
ModelDeltabar PMD78B
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals