Deltabar S FOUNDATION Fieldbus Installation
Endress+Hauser 17
When using a mounting bracket, sufficient strain relief must be ensured for the capillaries
in order to prevent the capillary bending down (bending radius 100 (3.94 in)).
Please observe the application limits of the diaphragm seal filling oil as detailed in the
Technical Information for Deltabar S TI00382P, "Planning instructions for diaphragm seal
systems" section.
NOTICE
In order to obtain more precise measurement results and to avoid a defect in the device,
mount the capillaries as follows:
Vibration-free (in order to avoid additional pressure fluctuations)
Not in the vicinity of heating or cooling lines
Insulate if the ambient temperature is below or above the reference temperature
With a bending radius of 100 mm (3.94 in).
Do not use the capillaries as a carrying aid for the diaphragm seals!
The ambient temperature and length of both capillaries should be the same when using
two-sided diaphragm seal systems.
Two diaphragm seals which are the same (e.g. with regard to diameter, material, etc.)
should always be used for the negative and positive side (standard delivery).
P01-FMD78xxx-11-xx-xx-xx-005
Fig. 2: Mounting Deltabar S, FMD78 with diaphragm seals and capillaries, recommended mounting for vacuum
applications: mount pressure transmitter below the lowest diaphragm seal!
Vacuum application (FMD78)
See operrating instructions.
+
+
100 mm