Installation Deltabar S FOUNDATION Fieldbus
16 Endress+Hauser
A condensate trap ensures constant pressure on the negative side.
When measuring in media with solid parts, such as dirty liquids, installing separators and
drain valves is useful for capturing and removing sediment.
Level measurement in a closed container with superimposed steam with FMD77
Mount the Deltabar S directly on the container. ä 18, Section 4.3.5 "Seal for flange
mounting".
Always connect the impulse piping of negative side above the maximum level.
A condensate trap ensures constant pressure on the negative side.
When measuring in media with solid parts, such as dirty liquids, installing separators and
drain valves is useful for capturing and removing sediment.
4.3.3 Installation for differential pressure measurement
Differential pressure measurement in gases and steam with PMD75
Mount the Deltabar S above the measuring point so that the condensate can run off into the
process piping.
Differential pressure measurement in liquids with PMD75
Mount the Deltabar S below the measuring point so that the pressure piping is always filled
with liquid and gas bubbles can run back into the process piping.
When measuring in media with solid parts, such as dirty liquids, installing separators and
drain valves is useful for capturing and removing sediment.
Differential pressure measurement in gases, steam and liquids with FMD78
Mount the diaphragm seal with capillaries at the top or on the side on the piping.
For vacuum applications: mount the Deltabar S below the measuring point. ä 17,
Section 4.3.4, "Vacuum application (FMD78)".
The ambient temperature should be the same for both capillaries.
4.3.4 Installation instructions for devices with diaphragm seals (FMD78)
Please note that the hydrostatic pressure of the liquid columns in the capillaries can cause
zero point shift. The zero point shift can be corrected.
Do not clean or touch the process isolating diaphragm of the diaphragm seal with hard or
pointed objects.
Do not remove process isolating diaphragm protection until shortly before installation.
Improper handling!
Damage to the device!
A diaphragm seal and the pressure transmitter together form a closed, oil-filled calibrated
system. The fill fluid hole is sealed and may not be opened.