Deltabar S
Endress+Hauser 15
Confirmation and locking
methods
The device is configured via the operating menu (see Operating Instructions BA00270P).
When using the devices in process control safety systems, the device configuration must meet two
requirements:
Confirmation concept:
Proven independent checking of safety-related parameters entered.
Via increased security during parameter entry or
Manually via a checklist
Locking concept:
Device locked after configuration (required in accordance with IEC 61511-1 §11.6.4 and NE 79 §3).
SIL locking via increased security during parameter entry and/or
Hardware locking via DIP switch on electronics; software locking
Two methods are available for commissioning the devices in process control safety systems:
Standard device configuration and hardware/software locking
Increased security during parameter entry
Due to the increased configuration security, the use of the "Increased security during parameter
entry" method is recommended.
Task
Select locking method SIL locking with increased security during parameter
entry (SAFETY CONFIRM. menu)
SW locking with standard configuration /
HW locking via DIP switch
Configuration
(e.g. LRV, URV, damping)
Via Quick Setup/operating menu Via Quick Setup/operating menu
Firmware 02.20.04
1)
Firmware 02.30.zz Firmware 02.20.04 Firmware 02.30.zz
Configuration
Alarm settings/messages
Message automatically
switched to alarm
Table ä 14
If required
(e.g. E727 pressure over-
range)
2)
E726 manually switched to
alarm, Table ä 14
If required
(e.g. E727 pressure over-
range)

Set current output/alarm
response
Automatic changeover
(e.g. to MAX alarm/
22 mA), Table ä 14
If required
MIN or MAX (default)
MIN or MAX (default)
Confirm plausibility and
correctness of parameter
settings
Automatically via SAFETY CONFIRM. menu Manually via checklist
Lock Automatically via SAFETY CONFIRM. menu
Additionally recommended: HW locking via DIP switch
SW locking with standard configuration and/or
HW locking via DIP switch
Operation FieldCare /
DeviceCare
Onsite display FieldCommuni-
cator
FieldCare /
DeviceCare
Onsite display FieldCommuni-
cator
Document DTM pdf Form ä 33ff DTM pdf Form ä 33ff
1) In the case of devices with firmware version 02.20.04, certain messages in the SAFETY CONFIRM. menu (increased security during parameter
entry) are automatically set from warning to alarm.
Do not use the SAFETY CONFIRM. sequence if the device is operated outside the set current or measuring range in applications, table ä 14.
2) Configuring E727 as a warning or alarm affects the SIL parameters, Table ä 4 ff.