The replaced component must be sent to Endress+Hauser for the purpose of fault analysis if the device
has been operated in a protective system.
In the event of the failure of a SIL-labeled Endress+Hauser device that has been operated in a protective
function, the "Declaration of Contamination and Cleaning" with the corresponding note "Used as SIL
device in protective system" must be enclosed when the defective device is returned. Please refer to the
"Return" section in the Operating Instructions (" ä 8", Supplementary device documentation).
Modification Modifications are changes to devices with SIL capability already delivered or installed.
Modifications to devices with SIL capability are usually performed in the Endress+Hauser
manufacturing center.
Modifications to devices with SIL capability onsite at the user's plant are possible
following approval by the Endress+Hauser manufacturing center. In this case, the modifications
must be performed and
documented by an Endress+Hauser service technician.
Modifications to devices with SIL capability by the user are not permitted.
Decommissioning When decommissioning, the requirements according to IEC 61508-1:2010 section 7.17 have to be
observed.
Cable gland EA00006P/00/A2 Proof-test 1
Proof-test 2
(alternative)
Clamp KA00602F/00/A2
Measuring range tag
Mounting kit EA00005P/00/A2
EA01016P/00/A2
KA00649P/00/A2
O-ring EA00005P/00/A2
Sensor
)
EA01007P/00/A2
EA01009P/00/A2
EA00005P/00/A2
Connector EA00006P/00/A2
1) Proof-test 2 must be applied.
Component Installation Instructions Checking the device after repair