Deltabar S
Endress+Hauser 37
Form for device configuration – Flow*
Operation via: Handheld terminal FieldCare/DeviceCare Onsite display
Device designation: Serial number:
Measuring point: Upper range limit (URL Sensor):
Parameter name Display ID Group Factory
setting
1)
Permitted
settings
Specified
value
Read-out
actual
value
Checked
Digits Set 840 Display 01234567890.-
Calib. Offset 319 Position Adjustm. 0.0
2)
Measuring Mode 389 Pressure Flow
Max. Flow 311 Quick Setup /
Basic Setup
1.0
3)
Max. Press. Flow 634 URL Sensor
) )
Damping Value 247 2.0 s 0 to 999 s
Press Eng. Unit 060 mbar / bar
),4)
all, except
"User unit"
Flow-Meas. Type 640 Basic Setup Volume p.
cond.
)
Unit Flow
),5)
391 m³/s all, except
"User unit"
Norm Flow Unit
), )
661 Nm³/s
Std. Flow Unit
), )
660 Sm³/s
Mass Flow Unit
), )
571 kg/s
Low Flow Cut-Off 442 Quick Setup /
Basic Setup /
Extended Setup
Off Off / On
Set L. Fl. Cut-Off 323 5% 0 to 50% of
Max. Flow
Set LRV
6)
637 0.0
)
Set URV
)
638 Max. Flow
)
Set LRV
7)
245 0.0
) )
Set URV
)
246 URL Sensor
) )
Curr. Charact. 695 Output Linear Linear
Output Fail Mode 388 Quick Setup /
Output
Max. Alarm Max. Alarm
Min. Alarm
Alt. Current Output 597 Normal Normal
Max. Alarm Current 342 Output 22 mA 21 to 23 mA
Set Min. Current 343 Quick Setup /
Output
3.8 mA 3.8 mA or
4.0 mA
Linear/Sqroot. 390 Output Flow (square
root)
Differential
pressure/ Flow
(square root)
Simulation 413 Simulation None None
*Not for options with measuring range, e.g. 160/250 bar [2320/3625 psi])