Deltabar S
38 Endress+Hauser
Ack. Alarm Mode 401 Messages Off Off / On
Error No. 595 / 600
115 Sensor over pressure Warning Alarm or Warning
120 Sensor low pressure Warning Alarm or Warning
715 Sensor over temperature Warning Alarm or Warning
717 Transmitter over temp. Warning Alarm or Warning
718 Transmitter under temp. Warning Alarm or Warning
720 Sensor under temperature Warning Alarm or Warning
726 Sens. temp. error overrange Warning/
alarm
8)
Alarm
727 Sens. pres. error overrange
9)
Warning Alarm or Warning
620 Current output out of range Warning Alarm or Warning
Alarm Delay 336 0.0 s 0.0 s
Alarm Displ. Time 480 0.0 s 0.0 s
Current Mode
10)
052 HART Data Signaling
11)
or
Enabled
12)
Signaling
)
or
Enabled
)
Bus address 345 0 0
After locking:
Config. Recorder
352 Transmitter data
1) After performing the reset with the reset code "7864"
2) Within sensor range
3) According to ordering specifications
4) Depending on the "Press. Sens. Hilim (485)" parameter
5) Only one value can be entered. This depends on the "Flow Meas. Type (640)" parameter.
6) Linear / Sqroot. = Flow (square root)
7) Linear / Sqroot. = Differential pressure
8) Alarm setting from firmware version 02.30.zz
9) Setting influences SFF
10) Only for software version 02.20
11) Onsite display and FieldCare
12) HART handheld terminal
Parameter name Display ID Group Factory
setting
1)
Permitted
settings
Specified
value
Read-out
actual
value
Checked
Company: Date: Signature: