Deltabar S
20 Endress+Hauser
Standard parameter entry
via onsite display,
Field Communicator or
FieldCare/DeviceCare
Standard device configuration via Field Communicator handheld terminal
a. Select "Main Menu" "HART Communication", in "Hart application" select "Online". The device
will automatically be found and opened online. Make sure that the bus address of the device
is = 0.
b. Make sure that the connection has been established to the correct device. This can be checked
using the measuring point, extended order code or serial number parameters.
Standard device configuration via the FieldCare/DeviceCare operating program
a. The connection can be established in the following two ways:
– Select the "HART communication" connection wizard. The device will automatically be
found and opened online. Make sure that the bus address of the device is = 0
– In the navigation tree, select "Create projects", then select "Add device" "HART
communication".
Then select "Create network". The device is opened online.
Make sure that the bus address of the device is = 0.
b. Make sure that the connection has been established to the correct device. This can be checked
using the measuring point, extended order code or serial number parameters.
In the case of device configuration via the onsite display, Field Communicator or FieldCare/DeviceCare,
perform the following steps:
1. Reset the parameters to their factory setting: with the "7864" reset code.
(Operating Instructions BA00270P/00/EN, "Factory setting (reset)" section).
Check default values, number formats and parameter designations using the "Form for device
configuration" (column "factory settings", ä 33ff).
The following operating steps may no longer be performed after this reset:
‣Position adjustment or setting the measuring range on site without using the onsite display
‣Download
‣Configuration backup using HistoROM
®
/M-DAT
‣Reset apart from reset code "7864"
‣Current trimming
‣Sensor recalibration ("note" ä 21)
2. By means of the DIGIT SETS parameter, check whether the characters and digits are displayed
correctly on the user interface. "0123456789.-" is displayed if everything is displayed correctly.
Menu path: (GROUP SELECTION) → OPERATING MENU → DISPLAY
3. Configure the device and log settings manually.
For the configuration Operating Instructions BA00270P/00/EN and BA00274P/00/EN.
Switch the device off and on again. This ensures that the parameter settings have been saved.
4. Check safety functions ("Checks" ä 22).
Restart FieldCare/DeviceCare or Handheld FieldCommunicator and reconnect device.
5. Read out the specified parameters and compare them to the "Form for device configuration"
ä 33ff.
6. Lock the device via software and/or hardware.
Operating Instructions BA00270P/00/EN, "Locking/unlocking operation" section.
7. Read out and log the CONFIG. COUNTER parameter.
Menu path: (GROUP SELECTION ) OPERATING MENU TRANSMITTER INFO
TRANSMITTER DATA
Observe the prescribed parameters in accordance with the "Form for device configuration:
• For "Pressure", ä 33
• For "Level" ("Level Easy Pressure" level selection) ä 35
• For "Flow", ä 37
In addition, the permitted parameter settings ä 21 must be taken into consideration.