Deltabar S
Endress+Hauser 19
For increased security during parameter entry via the FieldCare/DeviceCare operating program, perform
the following steps:
Perform steps 1 to 12, see ä 16 ff
13. Switch the device off and on again. This makes sure that parameter settings for the current ouput,
the alarm behavior and locking have been stored. Read the parameters out again and compare
them to the "Form for device configuration" ( ä 33ff).
For increased security during parameter entry via the Field Communicator handheld terminal, perform
the following steps:
Perform steps 1 to 12, see ä 16 ff
The "Offline" and "FDT-Up-Download" operating options are not allowed for functional safety
options.
Observe the status when entering or reading parameters. The status is represented by icons or
symbols and may indicate possible errors concerning the data input, the updating of parameters
or the connection to the device.
For further information, refer to the FieldCare help.
13. Switch the device off and on again. This makes sure that parameter settings for the current
ouput, the alarm behavior and locking have been stored. Read the parameters out again and
compare them to the "Form for device configuration" ( ä 33ff).
The "Offline" operating option is not allowed for functional safety applications. Make sure that no
messages such as "Device disconnected" occur during the configuration.