Deltabar S
18 Endress+Hauser
10. Only for firmware versions ≤ 02.20.04
By means of the OUTPUT CURRENT parameter, the user can check whether the following
parameters are correctly reset to the factory values. If reset correctly, the OUTPUT CURRENT
parameter displays "LinMaxNorm/22/3.8/0s". Factory values:
– CURR. CHARACT.: linear
– OUTPUT FAIL MODE: max. alarm
– ALT. CURR. OUTPUT: normal
– SET MAX. ALARM: 22 mA
– SET MIN. CURRENT: 3.8 mA
–ALARM DELAY: 0.0 s
– ALARM DISPLAY TIME: 0.0 s
Options:
– Valid: Select this option if the factory values displayed correspond to the desired values. The
system continues to interrogate the safety-related parameters.
– Not valid: Select this option if the factory values displayed do not correspond to the desired
values. In this case, operation in the safe measuring mode is not possible. The SAFETY LOCK
parameter displays the status "Unlocked". The confirmation sequence is aborted.
11. The following parameters have to be confirmed depending on the operating mode selected:
Options:
• Valid: Select this option if the value entered or the desired value is displayed. The system continues
to interrogate the safety-related parameters.
• Not valid: Select this option if an incorrect value or a value that was not entered is displayed. In this
case, operation in the safe measuring mode is not possible. The SAFETY LOCK parameter displays
the status "Unlocked". The confirmation sequence is aborted.
12. Once the safety-related parameters have been successfully interrogated, the password "7452"
must be entered again via the CONF. PASSWORD parameter. Afterwards, the device is locked for
the safe measuring mode. The SAFETY LOCK parameter displays the status "Locked". This locking
has the highest priority and can only be disabled via the SAFETY LOCK and SAFETY PASSWORD
parameters. ä 23, "Locking/unlocking" section.
For firmware version ≤ 02.20.04
– ACK. ALARM MODE
– CALIB. OFFSET
–MEASURING MODE
– PRESSURE EMPTY (only Level operating mode)
– EMPTY CALIB. (only Level operating mode)
– PRESSURE FULL (only Level operating mode)
– FULL CALIB. (only Level operating mode)
– MAX. FLOW (only Flow operating mode)
– MAX. PRESS. FLOW (only Flow operating mode)
– LOW FLOW CUT-OFF (only Flow operating mode)
– SET. L. FL. CUT-OFF (only Flow operating mode)
– LINEAR/SQROOT (only Flow operating mode)
–SET LRV
–SET URV
–DAMPING VALUE
For firmware version ≥ 02.30.zz
– ACK. ALARM MODE
– CALIB. OFFSET
–MEASURING MODE
– PRESSURE EMPTY (only Level operating mode)
– EMPTY CALIB. (only Level operating mode)
– PRESSURE FULL (only Level operating mode)
– FULL CALIB. (only Level operating mode)
– MAX. FLOW (only Flow operating mode)
– MAX. PRESS. FLOW (only Flow operating mode)
– LOW FLOW CUT-OFF (only Flow operating mode)
– SET. L. FL. CUT-OFF (only Flow operating mode)
– LINEAR/SQROOT (only Flow operating mode)
–SET LRV
–SET URV
–DAMPING VALUE
– OUPUT FAIL MODE
– SET MIN. CURRENT
– SET MAX. ALARM
– E727 P.OVERRANGE
The value saved is indicated on the fourth line of the onsite display.