Deltabar S
Endress+Hauser 33
Form for device configuration – Pressure
Operation via: Handheld terminal FieldCare/DeviceCare Onsite display
Device designation: Serial number:
Measuring point: Upper range limit (URL Sensor):
Parameter name Display ID Group Factory
setting
1)
Permitted
settings
Specified value Read-out
actual
value
Checked
Digits Set 840 Display 01234567890.-
Calib. Offset 319 Position Adjustm. 0.0
2)
Measuring Mode 389 Pressure Pressure
Set LRV 245 Quick Setup/
Basic Setup
0.0
3) )
Set URV 246 URL Sensor
) )
Damping Value 247 2.0 s 0 to 999 s
Press Eng. Unit 060 Basic Setup mbar / bar
),4)
all, except
"User unit"
Curr. Charact. 695 Output Linear Linear
Output Fail Mode 388 Max. alarm Max. alarm
Min. alarm
Alt. Current Output 597 Normal Normal
Max. Alarm Current 342 22 mA 21 to 23 mA
Set Min. Current 343 3.8 mA 3.8 mA or
4.0 mA
Simulation 413 Simulation None None
Ack. Alarm Mode 401 Messages Off Off / On
Error no., select alarm type
The following messages must be set
to "Alarm":
595 / 600
115 Sensor over pressure Warning Alarm or Warning
120 Sensor low pressure Warning Alarm or Warning
715 Sensor over temperature Warning Alarm or Warning
717 Transmitter over temp. Warning Alarm or Warning
718 Transmitter under temp. Warning Alarm or Warning
720 Sensor under temperature Warning Alarm or Warning
726 Sens. temp. error overrange Warning/
alarm
5)
Alarm
727 Sens. pres. error overrange
6)
Warning Alarm or Warning
620 Current output out of range Warning Alarm or Warning
Alarm Delay 336 0.0 s 0.0 s
Alarm Displ. Time 480 0.0 s 0.0 s