Deltabar S
32 Endress+Hauser
SET URV
(853)
For displaying and querying the value entered or calculated for the SET URV
parameter (BASIC SETUP or QUICK SETUP group).
Options:
Valid: Select this option if the entered and desired value is displayed.
Not valid: Select this option if a value that was not entered or desired is
displayed. In this case, operation of the device in the safe measuring mode is not
possible.
You can also configure the upper-range value via the GET URV parameter and
a pressure present at the device. The SET URV parameter displays the
pressure value that was assigned to the upper-range value.
DAMPING VALUE
(855)
For displaying and querying the value entered for the DAMPING VALUE parameter
(BASIC SETUP or QUICK SETUP group).
Options:
Valid: Select this option if the entered and desired value is displayed.
Not valid: Select this option if a value that was not entered or desired is
displayed. In this case, operation of the device in the safe measuring mode is not
possible.
Changing the "Damping" DIP switch on the electronic insert does not have any
effect on the damping time when operation for the safe measuring mode is
locked via SAFETY LOCK (836), SAFETY PASSWORD (838) and CONF.
PASSWORD (856). A change only takes effect once operation has been
unlocked.
CONF. PASSWORD
(856)
Once the safety-related parameters have been successfully interrogated, the
password " 7452" must be entered again via the CONF. PASSWORD parameter.
Afterwards, the device is locked for the safe measuring mode.
The SAFETY LOCKSTATE parameter displays the status "Locked".
MEASURING MODE = Pressure
Parameter name Description