Deltabar S
30 Endress+Hauser
OUTPUT FAIL MODE (57) Only if firmware version ≥ 2.30
For displaying and querying the set output fail mode.
Possibilities:
• Max. alarm (110 %)
• Min. alarm (-10 %)
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
SET MIN. CURRENT (56) Only if firmware version ≥ 2.30
For displaying and querying the lower current limit.
Possibilities:
•3.8 mA
•4.0 mA
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
SET MAX. ALARM (54) Only if firmware version ≥ 2.30
For displaying and querying the set current value for the maximum alarm current.
Possibilities:
• 21 to 23 mA
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
E727 P.OVERRANGE (58) Only if firmware version ≥ 2.30
For displaying and querying the behavior in the event of this error.
This setting affects the SIL characteristic values.
Possibilities:
• Alarm (A) output current adopts a defined value.
• Warning (W): output current in saturation (3.8 mA or 20.5 mA).
Options:
• Valid: Select this option if the selected and desired value is displayed.
• Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
MEASURING MODE = Pressure
Parameter name Description