Deltabar S
30 Endress+Hauser
OUTPUT FAIL MODE (57) Only if firmware version 2.30
For displaying and querying the set output fail mode.
Possibilities:
Max. alarm (110 %)
Min. alarm (-10 %)
Options:
Valid: Select this option if the selected and desired value is displayed.
Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
SET MIN. CURRENT (56) Only if firmware version 2.30
For displaying and querying the lower current limit.
Possibilities:
•3.8 mA
•4.0 mA
Options:
Valid: Select this option if the selected and desired value is displayed.
Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
SET MAX. ALARM (54) Only if firmware version 2.30
For displaying and querying the set current value for the maximum alarm current.
Possibilities:
21 to 23 mA
Options:
Valid: Select this option if the selected and desired value is displayed.
Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
E727 P.OVERRANGE (58) Only if firmware version 2.30
For displaying and querying the behavior in the event of this error.
This setting affects the SIL characteristic values.
Possibilities:
Alarm (A) output current adopts a defined value.
Warning (W): output current in saturation (3.8 mA or 20.5 mA).
Options:
Valid: Select this option if the selected and desired value is displayed.
Not valid: Select this option if an incorrect value or a value that was not selected
is displayed. In this case, operation of the device in the safe measuring mode is
not possible.
MEASURING MODE = Pressure
Parameter name Description

Other manuals for Endress+Hauser Deltabar S PMD75

Related product manuals