Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 11
3.4.3 Restrictions for safety-related operation
Device warm-up time: after device warm-up, the safety functions are available after a
30 Sekunden initialization period.
If the device is operated locally without a display and without an operating tool or
without a HART communicator, it cannot be safely configured because the user cannot
perform a visual check. In both these situations, communication via HART alone is not
sufficient.
The device must be locked after parameter configuration.
When the device is used as a subsystem of a safety function, the "Hold measured value"
setting in the "Output fail mode (388)" parameter and the Multidrop mode may not be
selected as this option does not guarantee a failsafe alarm.
A complete function test of the safety-related functions must be carried out during
commissioning.
The maximum interval for proof testing (proof test interval) is 5 Jahre.
Faulty devices must be replaced as soon as possible to minimize the possibility of
multiple errors occurring. The failure probabilities indicated in this Functional Safety
Manual are based on a medium time to repair (MTTR) of 8 Stunden.
3.5 Dangerous undetected failures in this scenario
An incorrect output signal that deviates from the real measured value by more than 1 %,
but is still in the 4 to 20 mA range, is considered a dangerous, undetected failure.
3.6 Useful lifetime of electric components
The established failure rates of electrical components apply within the useful lifetime as
per IEC 61508-2:2010 section 7.4.9.5 note 3.
According to DIN EN 61508-2:2011 section 7.4.9.5 (national footnote N3) appropriate
measures taken by the operator can extend the useful lifetime.
4 Commissioning (installation and
configuration)
4.1 Requirements for personnel
The personnel for installation, commissioning, diagnostics and maintenance must fulfill
the following requirements:
Trained, qualified specialists must have a relevant qualification for this specific function
and task.
Personnel must be authorized by the plant owner/operator.
Be familiar with federal/national regulations.
Before starting work: personnel must read and understand the instructions in the
manual and supplementary documentation as well as the certificates (depending on
the application).
Personnel must follow instructions and comply with general policies.
The operating personnel must fulfill the following requirements:
Personnel are instructed and authorized according to the requirements of the task by
the facility's owner-operator.
Personnel follow the instructions in this manual.