Appendix Deltapilot S FMB70
36 Endress+Hauser
8.2.2 Level device parameter configuration form
1)
Operation via: Handheld terminal FieldCare/DeviceCare On site
Device designation: Serial number:
Measuring
point:
Upper range limit (URL sensor):
Parameter name Direct
access
Menu path:
Expert
Factory setting
1)
Permitted
settings
Specifie
d value
Actual
value
Checked
Digits set 840 → Display 012345
67890.-
Calib. offset 319 → Position
adjustment
0.0
2)
Measuring mode 389 Pressure Level
Level selection 020 Level easy pressure Level easy pressure
Empty calib. 010 → Basic setup 0.0 % or as per order
Empty pressure 011 0.0 or as per order
2)
Full calib. 004 100 % or as per order
Full pressure 005 URL sensor or as per order
2)
Set LRV 013 0.0 % or as per order
Set URV 012 100 % or as per order
Damping value 247 2 s 0 to 999 s
Press. eng. unit 060 mbar/bar
or as per order
3)
All
except "user unit"
Output unit 023 % or as per order
Adjust density 007 → Extended setup 1.0 kg/dm³ = Process density
(025)
Current charact. 695 → Output Linear Linear
Output fail mode 388 Max. alarm Max. alarm
Min. alarm
Alt. curr. output 597 Normal Normal
Set max. alarm 342 22 mA 22 mA
Set min. current 343 3.8 mA 3.8 mA
Simulation 413 → Simulation None None
Ack. alarm mode 401 → Messages Off Off/On
Error No. Select alarm
type
The following messages
must be set to "Alarm":
595/600
115 Sensor over pressure Warning Alarm o. warning
120 Sensor low pressure Warning Alarm o. warning
715 Sensor over
temperature
Warning Alarm o. warning
717 Transmitter over
temp.
Warning Alarm o. warning
1) Not for options with measuring range e.g. 160/250 bar [2320/3625 psi])