Operation Deltapilot S FMB70
28 Endress+Hauser
Parameter Description Factory setting Parameterization method with increased
security during parameter entry
FW 02.20 FW ≥
02.30.zz
Permitted SIL
setting
FW ≤
02.20
1)
FW ≥ 02.30.zz
727 Sens. pres. error
overrange
2)
Warning Warning Warning or
alarm
Alarm As per client
setting
(default: warning)
Alarm
current
Output fail mode MAX MAX MIN. or MAX MAX As per client
setting
(default: MAX.)
1) Settings are automatically changed from warning to alarm via the parameterization method
2) The setting influences the parameters for functional safety
L
WARNING
In the case of devices with firmware version ≤ 02.20.04, certain messages in the
SAFETY CONFIRM. menu (increased security during parameter entry) are
automatically set from warning to alarm.
Do not use the SAFETY CONFIRM. sequence if the pressure in the applications is outside
the set current or measuring range.
‣
Standard device configuration and software/hardware locking is recommended in such
applications.
5.3.2 Device response in event of overranging
LRL -10% URL +10%
LRL
URL
LRV
1
2
3
5
URV
A
B
4
A0022894
A Range of current signal for measured value transmission (NE43) 3.8 to 20.5 mA
B Range of output current ≤3.6 to ≥21.0 mA
LRL Lower range limit
LRV Lower range value
URV Upper range value
URL Upper range limit
Process pressure range Acting process
pressure
Message
1)
1 Process pressure below
sensor measuring range
limit
E120 (LRL - 10%)
E727 (<< LRL - 10%)
2 Process pressure/
current below set range
limit
E620 < LRV
3 Process pressure within
set measuring range
None (3.8 to 20.5 mA
4 Process pressure/
current above set range
limit
E620 > URV
5 Process pressure above
sensor measuring range
limit
E115 (URL + 10%)
E727 (>> URL + 10%)
1) The output current depends on the message setting as alarm or warning