Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 21
15. Once the safety-related parameters have been successfully interrogated, the
password "7452" must be entered again via the CONF. PASSWORD parameter.
Afterwards, the device is locked for the safe measuring mode. The SAFETY LOCK
parameter displays the status "Locked". This locking has the highest priority and can
only be disabled via the SAFETY LOCK and SAFETY PASSWORD parameters.
16. Switch the device off and then on again. This ensures that the parameter settings for
the current output, alarm response and locking are saved. Read out the parameters
again and compare them to the data recorded in the "Device parameter configuration
report".
The "Offline" operating function and FDT-Up-Download are not permitted for the
configuration of an application with functional safety.
Note the status when entering and displaying the parameters. This is indicated by
icons/symbols and refers to possible errors during parameter entry, when updating
parameters and when connecting to the device. More information can be found in
the FieldCare help.
Standard parameter configuration
Parameter configuration via local display
1. Reset parameters to factory setting: reset code "7864" (see the associated Operating
Instructions, "Resetting to factory setting (reset)" section). Check default values,
number formats and parameter descriptions with the "Device parameter
configuration report".
After this reset, the following operating steps may no longer be performed:
Position adjustment or onsite configuration of measuring range without local
display
Download
Configuration backup with HistoROM®/M-DAT
Reset, except for reset code "7864"
Current trim
Sensor recalibration
2. Via the DIGIT SETS parameter, check whether the characters and digits are displayed
correctly on the user interface. "0123456789.-" is shown if everything is displayed
correctly. Menu path: (GROUP SELECTION →) OPERATING MENU → DISPLAY
3. Configure the device parameters and keep a manual log of the settings. For
parameter configuration, see the associated Operating Instructions. Switch the device
off and then on again. This ensures that the parameter settings have been saved.
Observe the prescribed parameters in accordance with the "Device parameter
configuration form". The permitted parameter settings must also be taken into
consideration.
4. Check the safety function.
5. Read out the prescribed parameters and compare them to the "Device parameter
configuration report".
6. Lock the device via the software and/or hardware (see the associated Operating
Instructions).