Deltapilot S FMB70 Commissioning (installation and configuration)
Endress+Hauser 23
9. Read out and keep a record of the CONFIG RECORDER parameter. Menu path:
(GROUP SELECTION→) OPERATING MENU → TRANSMITTER INFO →
TRANSMITTER DATA
If the device is in a fault state, i.e. an alarm is output and the current output adopts
the set value, the cause of the fault must first be eliminated.
"Level" operating mode, "Level easy pressure" level selection: The EMPTY PRESSURE
and FULL PRESSURE parameters are only displayed for the "Dry" CALIBRATION
MODE.
If you have performed a wet calibration, you must subsequently select the "Dry"
option via the CALIBRATION MODE parameter. You can read out the corresponding
values for the EMPTY PRESSURE and FULL PRESSURE parameters here.
The sensor can only be recalibrated by Endress+Hauser Service. All parameters,
except the parameters for a sensor recalibration, are reset by the "7864" reset code.
Therefore, the parameters have to be checked prior to locking via the SAFETY
CONFIRM. menu.
Parameter configuration via FieldCare operating program
1. The connection can be established in the following two ways: 1) Select the "HART
Communication" connection wizard. The device will then be found automatically and
opened online. Ensure that the device bus address = 0. 2) In the tree structure, select
"Create projects" → "Add device" → "HART communication" and then select "Create
network". The device is opened online. Ensure that the device bus address = 0.
2. Ensure that the connection has been made with the correct device. This can be done
using the "Measuring point" parameter, the extended order number or the serial
number.
3. Reset parameters to factory setting: reset code "7864" (associated Operating
Instructions, "Resetting to factory setting (reset)" section). Check default values,
number formats and parameter descriptions with the "Device parameter
configuration report".
After this reset, the following operating steps may no longer be performed:
Position adjustment or onsite configuration of measuring range without local
display
Download
Configuration backup with HistoROM®/M-DAT
Reset, except for reset code "7864"
Current trim
Sensor recalibration
4. Via the DIGIT SETS parameter, check whether the characters and digits are displayed
correctly on the user interface. "0123456789.-" is shown if everything is displayed
correctly. Menu path: (GROUP SELECTION →) OPERATING MENU → DISPLAY
5. Configure the device parameters and keep a manual log of the settings. For
parameter configuration, see the associated Operating Instructions. Switch the device
off and then on again. This ensures that the parameter settings have been saved.
Observe the prescribed parameters in accordance with the "Device parameter
configuration form". The permitted parameter settings must also be taken into
consideration.
6. Check the safety function. Close FieldCare. Then connect to the device again.
7. Read out the prescribed parameters and compare them to the "Device parameter
configuration report".
8. Lock the device via the software and/or hardware (see the associated Operating
Instructions)