Deltapilot S FMB70 Appendix
Endress+Hauser 39
Parameter name Description
OUTPUT FAIL MODE
(57)
Only for firmware version ≥ 2.30
For displaying and querying the set output fail mode.
Possibilities:
• Max. alarm (110 %)
• Min. alarm (–10 %)
Options:
• Valid
Select this option if the selected and desired value is displayed
• Not valid
Select this option if an incorrect value or a value that was not selected is displayed. In this case, operation
in the safe measuring mode is not possible.
SET MIN. CURRENT
(56)
Only for firmware version ≥ 2.30
For displaying and querying the lower current limit.
Possibilities:
• 3.8 mA
• 4 mA
Options:
• Valid
Select this option if the selected and desired value is displayed
• Not valid
Select this option if an incorrect value or a value that was not selected is displayed. In this case, operation
in the safe measuring mode is not possible.
SET MAX. ALARM
(54)
Only for firmware version ≥ 2.30
For displaying and querying the set current value for the maximum alarm current.
Possibilities:
21 to 23 mA
Options:
• Valid
Select this option if the selected and desired value is displayed
• Not valid
Select this option if an incorrect value or a value that was not selected is displayed. In this case, operation
in the safe measuring mode is not possible.
E727 P.OVERRANGE
(58)
Only for firmware version ≥ 2.30
For displaying and querying the set behavior in the event of this error. This setting affects the SIL
characteristic values.
Possibilities:
• Alarm (A): output current adopts a defined value
• Warning (W): output current in saturation (3.8 or 20.5 mA)
Options:
• Valid
Select this option if the selected and desired value is displayed
• Not valid
Select this option if an incorrect value or a value that was not selected is displayed. In this case, operation
in the safe measuring mode is not possible.