Levelflex FMP53
Endress+Hauser 41
Mounting at an angle
a
LN
A0014145
For mechanical reasons, the probe should be installed as vertically as possible.
If the probe is installed at an angle, the length of the probe must be reduced depending on the
angle of installation.
α 5 °: LN
max.
4 m (13.1 ft)
α 10 °: LN
max.
2 m (6.6 ft)
α 30 °: LN
max.
1 m (3.3 ft)