Liquistation CSF33 Operation
Endress+Hauser 81
Menu/Setup/Sampling programs
Function Options Info
Sampling mode Selection
Time paced CTCV
Flow paced VTCV
Time/flow paced CTVV
External signal
Factory setting
Time paced CTCV
A constant sampling volume is taken at
steady intervals.
Flow paced VTCV
A constant sampling volume is taken at
variable intervals. Time override can be
enabled in an advanced program. With time
monitoring, it is possible to interrupt long,
flow-controlled sampling intervals caused by
a low flow rate. A sample which is also time-
controlled is taken.
Time/flow paced CTVV
(only for version with peristaltic pump)
A variable sampling volume is taken at
steady intervals.
External signal
A pulse at the binary input starts a sampling
cycle.
The settings that depend on the sampling mode are listed in the "Program type: Basic" section.
Enable subprogram Selection
Immediate
Individual dates
Repeating date
Interval
Deactivation
Factory setting
Immediate
Immediate
The subprogram is enabled immediately.
Individual dates
Set the start and stop dates for enabling the
subprogram.
Repeating date
Set the start condition, activity time and
repetition interval for the subprogram.
Interval
Set the start condition, activity time and
inactivity time for the subprogram.
Deactivation
Subprogram 2 or 2+n is started as soon as
subprogram 1 is disabled. Only possible with
multiple subprograms.
Having selected Enable subprogram Individual dates
Individual dates
Set the start and stop times for the subprogram. Enter a new date via "INSERT". Delete a date via
"DELETE". You can assign a maximum of 25 start and stop dates.
Having selected Enable subprogram Repeating date
Start condition Selection
No delay
Date/Time
Time
No delay (sync)
Factory setting
No delay (sync)
No delay
The subprogram is started when the
program is enabled.
Date/Time
Set the start date and start time for enabling
the subprogram.
Time
Set the start time for enabling the
subprogram.
No delay (sync)
Only possible on program start Immediate
and with bottle assignment "Dynamic or
Static".
Activity time 00:01 to 99:59 HH:MM
Factory setting
00:01 HH:MM
Specify how long the subprogram should be
active in hours and minutes. The time to be
selected depends on the setting for the
repetition mode.