Liquisys M CPM223/253 Commissioning
Endress+Hauser 67
R259
Enter number of
cleaning cycles
without cleaning
agent (economy
function)
0
0to9
After cleaning with cleaner, up to 9
cleaning sessions can be carried out with
water only until the next cleaning session
with cleaner takes place.
R2 (6)
Configure
neutralisation
controller
LC PV = limit contactor pH/
ORP (1)
LC C = limit contactor T (2)
PID controller (3)
Timer (4)
Clean = Chemoclean (5)
Neutra controller (6)
Only for A1 = pH.
If neutra controller is selected for Rel1,
only neutra controller is offered for Rel2.
By confirming with ENTER, another relay
function already switched on is switched
off and its settings are reset to the factory
settings.
R261
Switch function of
R2 (6) off or on
Off
On
R262
Enter set point 1 (or
2)
pH 6.00
pH -2.00 to 16.00
Relay assignment 1 and 2 for neutra
controller:
Rel1 = set point 1
Rel2 = set point 2
R263
Enter relay switching
capacity K
p
1 (or K
p
2)
1.00
0.10 to 20.00
Relay assignment 1 and 2 for neutra
controller:
Rel1 = Kp1
Rel2 = Kp2
R264
Enter integral action
time T
n
1 (or T
n
2)
(0.0 = no I-
component)
0.0 min
0.0 to 999.9 min
Relay assignment 1 and 2 for neutra
controller:
Rel1 = Tn1
Rel2 = Tn2
R265
Enter derivative
action time T
v
1 (or
T
v
2)
(0.0 = no D-
component)
0.0 min
0.0 to 999.9 min
Relay assignment 1 and 2 for neutra
controller:
Rel1 = Tv1
Rel2 = Tv2
R266
Select pulse length
or pulse frequency
Len = pulse length
Freq = pulse frequency
Curr = current output 2
Pulse length e.g. for solenoid valve, pulse
frequency e.g. for solenoid dosing pump,
see "Actuating signal outputs" section.
Curr = current output 2 can only be
selected if O2 = Contr.
R267 Enter pulse interval
10.0 s
0.5 to 999.9 s
This field only appears if pulse length is
selected in R266.
If pulse frequency is selected, R267 is
skipped and entries continue with R268.
Coding Field Setting range
(Factory settings, bold)
Display Info