Micropilot FMR56, FMR57
14 Endress+Hauser
Input values Analog Output:
• Analog value from PLC (for sensor block, external pressure to compensate for gas
phase effects)
• Analog value from PLC for transmission to display
Digital Output:
• Extended Diagnostic Block
• Level Limiter
• Sensor Block Measurement On
• Sensor Block Save History On
• Status output
Supported functions • Identification & Maintenance
Simplest device identification on the part of the control system and nameplate
• Automatic Ident Number Adoption
GSD compatibility mode with predecessor Micropilot M FMR2xx
• Physical Layer Diagnostics
Installation check of the PROFIBUS segment and the Micropilot FMR5x using terminal
voltage and message monitoring
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS upload/
download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing diagnostic
messages that occur
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Device type 0x1028
Device revision 0x01
DD revision Information and files under:
• www.endress.com
• www.fieldcommgroup.org
CFF revision
Device Tester Version (ITK version) 6.0.1
ITK Test Campaign Number IT085300
Link Master capability (LAS) Yes
Choice of "Link Master" and "Basic Device" Yes; Factory setting: Basic Device
Node address Factory setting: 247 (0xF7)
Supported functions The following methods are supported:
• Restart
• ENP Restart
• Setup
• Linearization
• Self Check
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of link objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities