Micropilot FMR56, FMR57
16 Endress+Hauser
Block Contents Number of
permanent
blocks
Number of
instantiatable
blocks
Execution
time
Functionality
Multiple
Analog Output
Block
The Multiple Analog Output
Block is used to transmit analog
values from the bus to the device.
1 0 20 ms Standard
Multiple
Discrete
Output Block
The Multiple Discrete Output
Block is used to transmit discrete
values from the bus to the device.
1 0 20 ms Standard
PID Block The PID Block is used as a
proportional-integral-derivative
controller and can be used
universally for closed-loop-
control in the field. It enables
cascade mode and feedforward
control.
1 1 25 ms Standard
Arithmetic
Block
The Arithmetic Block is designed
to permit simple use of popular
measurement math functions.
The user does not have to know
how to write equations. The
math algorithm is selected by
name, chosen by the user for the
function to be performed.
1 1 25 ms Standard
Signal
Characterizer
Block
The Signal Characterizer Block
has two sections, each with an
output value that is a non-linear
function of the input value. The
non-linear function is generated
by a single look-up table with 21
arbitrary x-y pairs.
1 1 25 ms Standard
Input Selector
Block
The Input Selector Block
facilitates the selection of up to
four inputs and generates an
output value based on the
configured action. This block
normally receives its inputs from
AI Blocks. The block enables the
selection of maximum, minimum,
average and ‘first good’ values.
1 1 25 ms Standard
Integrator
Block
The Integrator Block integrates a
variable as a function of the time
or accumulates the counts from a
Pulse Input Block. The Block can
be used as a totalizer that
totalizes until a reset, or as a
batch totalizer whereby the
integrated value is compared
against a target value generated
before or during the control
routine and generates a binary
signal when the target value is
reached.
1 1 25 ms Standard
Analog Alarm
Block
1 1 25 ms Standard
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated.