Electrical connection
Terminal assignment
FTR525 ordering feature
-*1* -*2* -*3* -*4*
I+
A
I-
I+
Current output
• 4 ... 20 mA (passive)
• max. 22 mA
max. 28 V DC
I-
C+
C+
C-
Open Collector
• max. 28 V DC
• max. 200 mA
C-
3
NO (3/15)
CC (4/16)
NC (5/17)
Relay 1
• max. 250 V AC / 40 V DC
• max. 2 A
4
5
15
Relay 2
• max. 250 V AC / 40 V DC
• max. 2 A
16
17
3
3/15
4/16
SSR 1
• max. 30 V AC / 40 V DC
• max. 400 mA
4
15
SSR 2
• max. 30 V AC / 40 V DC
• max. 400 mA
16
6�3 Post-connection check
Is the device or line damaged (visual inspection)?

Are all terminals securely clicked into place in their correct slots?
Is the coding on the individual terminals correct?
Are the cables installed with strain relief?
Are the supply voltage and signal cables connected correctly?

Table of Contents