Commissioning
8�6�1 Simulation mode
Diagnose
1000
Simulation
1700
Simulation mode
1710

values and signal outputs).

"Current output", "Switching contact 1", "Switching contact 2", "Failure contact"
8�6�2 Simulation value
Diagnose
1000
Simulation
1700
Simulation value
1720
This function is used to enter corresponding simulation values for the selected simulation

Options: Measurement limit 0 to 100 %, measurement motion 0 to 100 %,
current output 3.6 to 22.0 mA, contact 3-4 opened, contact 3-4 closed,
contact 15-16 opened, contact 15-16 closed, failure, no failure
Simulation Simulation
value
Beschreibung
Measurement
limit 0-100%
Measurement
limit 0 to 100 %
A corresponding measurement is simulated by press-

All signal outputs follow the simulated value accord-
ing to the settings.
Measurement
motion 0-100%
Measurement
motion 0 to
100 %
Current output Current output
3�6 to 22�0 mA
A corresponding current output value is simulated by

All other outputs follow the original settings.
Switching
contact 1
Contact 3-4
opened
Contact 3-4
closed
Contact 3-4 of switching contact 1 is alternately

All other outputs follow the original settings.
Switching
contact 2
Contactt 15-16
opened
Contact 15-16
closed
Contact 15-16 of switching contact 2 is alternately

All other outputs follow the original settings.
This simulation is only available on FTR525 with two
switching outputs (relay or SSR).
Failure contact No failure
Failure
The failure contact (C+/C-) is alternately opened or

All other outputs follow the original settings.
O • The simulation is deactivated.
All other outputs follow the original settings.