Proline Promass P 300
Endress+Hauser 11
Digital communication
The measured values can be written from the automation system to the measuring via:
FOUNDATION Fieldbus
PROFIBUS DP
PROFIBUS PA
Modbus RS485
EtherNet/IP
PROFINET
Current input 0/4 to 20 mA
Current input 0/4 to 20 mA (active/passive)
Current span 4 to 20 mA (active)
0/4 to 20 mA (passive)
Resolution 1 µA
Voltage drop Typically: 0.6 to 2 V for 3.6 to 22 mA (passive)
Maximum input voltage ≤ 30 V (passive)
Open-circuit voltage ≤ 28.8 V (active)
Possible input variables Pressure
Temperature
Density
Status input
Maximum input values DC –3 to 30 V
If status input is active (ON): R
i
>3 kΩ
Response time Adjustable: 5 to 200 ms
Input signal level Low signal: DC –3 to +5 V
High signal: DC 12 to 30 V
Assignable functions Off
Reset the individual totalizers separately
Reset all totalizers
Flow override