Proline Promass P 300
Endress+Hauser 19
Web server
Plain text display With information on cause and remedial measures
Light emitting diodes (LED)
Status information Status indicated by various light emitting diodes
The following information is displayed depending on the device version:
• Supply voltage active
• Data transmission active
• Device alarm/error has occurred
• EtherNet/IP network available
• EtherNet/IP connection established
• PROFINET network available
• PROFINET connection established
• PROFINET blinking feature
Ex connection data Safety-related values
Order code for
"Output; input 1"
Output type Safety-related values
"Output; input 1"
26 (+) 27 (–)
Option BA Current output
4 to 20 mA HART
U
N
= 30 V
DC
U
M
= 250 V
AC
Option GA PROFIBUS PA U
N
= 30 V
DC
U
M
= 250 V
AC
Option LA PROFIBUS DP U
N
= 30 V
DC
U
M
= 250 V
AC
Option MA Modbus RS485 U
N
= 30 V
DC
U
M
= 250 V
AC
Option SA FOUNDATION Fieldbus U
N
= 30 V
DC
U
M
= 250 V
AC
Option NA EtherNet/IP U
N
= 30 V
DC
U
M
= 250 V
AC
Option RA PROFINET U
N
= 30 V
DC
U
M
= 250 V
AC
Order code for
"Output; input 2";
"Output; input 3"
Output type Safety-related values
Output; input 2 Output; input 3
24 (+) 25 (–) 22 (+) 23 (–)
Option B Current output
4 to 20 mA
U
N
= 30 V
DC
U
M
= 250 V
AC
Option D User configurable input/
output
U
N
= 30 V
DC
U
M
= 250 V
AC
Option E Pulse/frequency/switch
output
U
N
= 30 V
DC
U
M
= 250 V
AC
Option F Double pulse output U
N
= 30 V
DC
U
M
= 250 V
AC
Option H Relay output U
N
= 30 V
DC
I
N
=100 mA
DC
/500 mA
AC
U
M
= 250 V
AC
Option I Current input 4 to 20 mA U
N
= 30 V
DC
U
M
= 250 V
AC
Option J Status input U
N
= 30 V
DC
U
M
= 250 V
AC