Proline Promass P 300
Endress+Hauser 17
The technical values correspond to those of the inputs and outputs described in this section.
Signal on alarm
Depending on the interface, failure information is displayed as follows:
HART current output
Device diagnostics Device condition can be read out via HART Command 48
PROFIBUS PA
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
Failure current FDE (Fault
Disconnection Electronic)
0 mA
PROFIBUS DP
Status and alarm
messages
Diagnostics in accordance with PROFIBUS PA Profile 3.02
EtherNet/IP
Device diagnostics Device condition can be read out in Input Assembly
PROFINET
Device diagnostics According to "Application Layer protocol for decentralized periphery", Version 2.3
FOUNDATION Fieldbus
Status and alarm
messages
Diagnostics in accordance with FF-891
Failure current FDE (Fault
Disconnection Electronic)
0 mA
Modbus RS485
Failure mode Choose from:
NaN value instead of current value
Last valid value
Current output 0/4 to 20 mA
4 to 20 mA
Failure mode Choose from:
4 to 20 mA in accordance with NAMUR recommendation NE 43
4 to 20 mA in accordance with US
Min. value: 3.59 mA
Max. value: 22.5 mA
Freely definable value between: 3.59 to 22.5 mA
Actual value
Last valid value