Proline Promass P 300
16 Endress+Hauser
Double pulse output
Function Double pulse
Version Open collector
Can be set to:
Active
Passive
Maximum input values DC 30 V, 250 mA (passive)
Open-circuit voltage DC 28.8 V (active)
Voltage drop For 22.5 mA: ≤ DC 2 V
Output frequency Adjustable: 0 to 1 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1
Assignable measured
variables
Mass flow
Volume flow
Corrected volume flow
Density
Reference density
Temperature
The range of options increases if the measuring device has one or more
application packages.
Relay output
Function Switch output
Version Relay output, galvanically isolated
Switching behavior Can be set to:
NO (normally open), factory setting
NC (normally closed)
Maximum switching
capacity (passive)
DC 30 V, 0.1 A
AC 30 V, 0.5 A
Assignable functions Off
On
Diagnostic behavior
Limit value
Mass flow
Volume flow
Corrected volume flow
Density
Reference density
Temperature
Totalizer 1-3
Flow direction monitoring
Status
Partially filled pipe detection
Low flow
The range of options increases if the measuring device has one or more
application packages.
User configurable input/output
One specific input or output is assigned to a user-configurable input/output (configurable I/O)
during device commissioning.
The following inputs and outputs are available for assignment:
Choice of current output: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Pulse/frequency/switch output
Choice of current input: 4 to 20 mA (active), 0/4 to 20 mA (passive)
Status input