Proline Promass P 300
24 Endress+Hauser
ITK Test Campaign Number Information:
www.endress.com
www.fieldbus.org
Link Master capability (LAS) Yes
Choice of "Link Master" and
"Basic Device"
Yes
Factory setting: Basic Device
Node address Factory setting: 247 (0xF7)
Supported functions The following methods are supported:
Restart
ENP Restart
Diagnostic
Set to OOS
Set to AUTO
Read trend data
Read event logbook
Virtual Communication Relationships (VCRs)
Number of VCRs 44
Number of link objects in VFD 50
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Device Link Capabilities
Slot time 4
Min. delay between PDU 8
Max. response delay 16
System integration Information regarding system integration: Operating Instructions →  110.
Cyclic data transmission
Description of the modules
Execution times
Methods
Modbus RS485
Protocol Modbus Applications Protocol Specification V1.1
Response times Direct data access: typically 25 to 50 ms
Auto-scan buffer (data range): typically 3 to 5 ms
Device type Slave
Slave address range 1 to 247
Broadcast address range 0
Function codes 03: Read holding register
04: Read input register
06: Write single registers
08: Diagnostics
16: Write multiple registers
23: Read/write multiple registers
Broadcast messages Supported by the following function codes:
06: Write single registers
16: Write multiple registers
23: Read/write multiple registers