Prosonic Flow 92 11 Description of device functions
Endress+Hauser 71
Sensor Config. Use this function to select the configuration for the ultrasonic sensors, e.g.
the number of traverses.
Options:
1 traverse
2 traverse
4 traverse
Factory setting:
2 traverse
Sound Velovity This line displays the calculated sound velocity for the liquid, i. e. the calcu-
lated value resulting from the selections liquid and temperature which was
made in the liquid menu.
In case of Liquid “Others” will the display show the numbers entered in the
menu “Others”.
Viscosity This line displays the calculated viscocity for the liquid, i. e. the calculated
value resulting from the selections liquid and temperature which was made in
the liquid menu.
In case of Liquid “Others” will the display show the numbers entered in the
menu “Others”.
Sensor Type Please enter the sensor type you connected here.
Options:
W-CL-1F-L-B
W-CL-2F-L-B
P-CL-1F-L-B
P-CL-2F-L-B
P-CL-1F-M-B
P-CL-2F-M-B
U-CL-2F-L-A
Factory setting:
U-CL-2F-L-A
Note!
The U sensor is designed for 2 traverses only. Please ensure that “NO.
TRAVERSE: 2” is selected for the number of traverses in the SENSOR CON-
FIGURATION function (see Page 71).
Burst Voltage Use this function to select the burst voltage.
Options:
x1 – x2 – x4 – x8
Factory setting:
x1
Note!
After completing all entries, exit the function group “SITE DATA” by pressing the “ESC” key. The sensor
distance required for the installation of clamp-on sensors will be displayed in the bottom screen section
of the group “SITE SETUP”.
Site Setup Site Data