Prosonic S FMU90 PROFIBUS DP Installation
Endress+Hauser 15
5.2 Mounting the aluminum field housing
Valid for:
Order code 030 (housing, material)
Option 3 (aluminum field mounting, IP66 NEMA4x)
5.2.1 Installation conditions
Dimensions of the aluminum field housing
A0033258
 9 Dimensions of Prosonic S with aluminum field housing. Unit of measurement mm (in)
Mounting location
Shaded location, protected from direct sunlight
If mounting outdoors: use a surge arrester
Altitude: install at a maximum altitude of 2 000 m (6 560 ft) over MSL
Minimum clearance to the left: 55 mm (2.17 in); the housing cover cannot be opened
otherwise