Electrical connection Prosonic S FMU90 PROFIBUS DP
26 Endress+Hauser
Terminals for temperature input
Terminal area D
Terminals 83, 84, 85:
Pt100
Omnigrad S TR61 (Endress+ Hauser)
Other elements on the terminal areas
Terminal area A
Display
Connection of the display or the remote display and operating module
Service
Service interface; for connection of a PC/notebook via Commubox FXA291
Write protection switch: locks the device to prevent modifications to the configuration.
6.3 Special connection instructions
6.3.1 Connecting the power supply
L
CAUTION
To guarantee electrical safety:
Fix the power supply cables securely in place when installing so they are permanently
connected to the electrical installations for the building.
When connecting to the public mains, install a mains switch for the device such that it
is within easy reach of the device. Mark the power switch as a disconnector for the
device (IEC/EN61010).
For the 90-253VAC version: connect potential equalization
Switch off the supply voltage before connecting.
Connection of the power supply in the polycarbonate field housing
Valid for:
Order code 030 (housing, material)
Option 1 (PC field mounting, IP66 NEMA4x)