Commissioning Prosonic S FMU90 PROFIBUS DP
74 Endress+Hauser
AI 8
Bytes 35 - 38: Overflow totalizer 1 (IEEE754)
Byte 39: Status totalizer 1
AI 9
Bytes 40 - 43: Value totalizer 2 (IEEE754)
Byte 44: Status totalizer 2
AI 10
Bytes 45 - 48: Overflow totalizer 2 (IEEE754)
Byte 49: Status totalizer 2
"Level+Flow" operating mode
AI 1
Bytes 0 - 3: Flow 1 (IEEE754); unit: m
Byte 4: Status flow 1
AI 2
Bytes 5 - 8: Flow 2 (IEEE754); unit: m
Byte 9: Status flow 2
AI 3
Bytes 10 - 13: Level 1 (IEEE754); unit: m
Byte 14: Status level 1
AI 4
Bytes 15 - 18: Level 2 (IEEE754); unit: m
Byte 19: Status level 2
AI 5
Bytes 20 - 23: Temperature 1 (IEEE754); unit: °C
Byte 24: Status temperature 1
AI 6
Bytes 25 - 28: Temperature 2 (IEEE754); unit: °C
Byte 29: Status temperature 2
AI 7
Bytes 30 - 33: Value totalizer 1 (IEEE754)
Byte 34: Status totalizer 1
AI 8
Bytes 35 - 38: Overflow totalizer 1 (IEEE754)
Byte 39: Status totalizer 1
AI 9
Bytes 40 - 43: Value totalizer 2 (IEEE754)
Byte 44: Status totalizer 2
AI 10
Bytes 45 - 48: Overflow totalizer 2 (IEEE754)
Byte 49: Status totalizer 2
Changing the assigned measured variables
Parameter: Output/calculat. → Analog input → Analog input N → Measured value N
9.5 Simulation
9.5.1 Flow simulation
Navigation
For flow sensor:
Flow → Flow → Flow N → Simulation
For upstream sensor in event of backwater or dirt detection:
Flow → Flow 1 + backwater → Flow → Flow 1 → Simulation
For downstream sensor in event of backwater or dirt detection:
Flow → Flow 1 + Backwater → Backwater → Simulation