Prosonic S FMU90 PROFIBUS DP Commissioning
Endress+Hauser 73
AI 6
Bytes 25 - 28: Overflow totalizer 1 (IEEE754)
Byte 29: Status totalizer 1
AI 7
Bytes 30 - 33: Value daily counter 1 (IEEE754)
Byte 34: Status daily counter 1
AI 8
Bytes 35 - 38: Overflow daily counter 1 (IEEE754)
Byte 39: Status daily counter 1
Default configuration of the cyclic data telegram (2-channel version)
Valid for FMU90 - *****2***
"Level" operating mode
AI 1
Bytes 0 - 3: Level 1 (IEEE754); unit: m
Byte 4: Status level 1
AI 2
Bytes 5 - 8: Level 2 (IEEE754); unit: m
Byte 9: Status level 2
AI 3
Bytes 10 - 13: Distance 1 (IEEE754); unit: m
Byte 14: Status distance 1
AI 4
Bytes 15 - 18: Distance 2 (IEEE754); unit: m
Byte 19: Status distance 2
AI 5
Bytes 20 - 23: Temperature 1 (IEEE754); unit: °C
Byte 24: Status temperature 1
AI 6
Bytes 25 - 28: Temperature 2 (IEEE754); unit: °C
Byte 29: Status temperature 2
"Flow" operating mode
AI 1
Bytes 0 - 3: Flow 1 (IEEE754); unit: m
Byte 4: Status flow 1
AI 2
Bytes 5 - 8: Flow 2 (IEEE754); unit: m
Byte 9: Status flow 2
AI 3
Bytes 10 - 13: Distance 1 (IEEE754); unit: m
Byte 14: Status distance 1
AI 4
Bytes 15 - 18: Distance 2 (IEEE754); unit: m
Byte 19: Status distance 2
AI 5
Bytes 20 - 23: Temperature 1 (IEEE754); unit: °C
Byte 24: Status temperature 1
AI 6
Bytes 25 - 28: Temperature 2 (IEEE754); unit: °C
Byte 29: Status temperature 2
AI 7
Bytes 30 - 33: Value totalizer 1 (IEEE754)
Byte 34: Status totalizer 1