Prosonic S FMU90 PROFIBUS DP Commissioning
Endress+Hauser 53
9.3 Configuring the measuring device
9.3.1 Navigation to the menu "Basic setup"
Operating mode: "Level+flow" or "Flow"
Flow → Flow → Flow N → Basic setup
Operating mode: "Flow+backwater detection"
Flow → Flow 1 +backwater → Flow → Basic setup
9.3.2 Parameter set "Sensor selection"
Navigation
Basic setup → Sensor selection
Parameter
• Input
Assign a sensor to the channel.
• Sensor selection
Specify the sensor type.
Select the Automatic option for FDU9x sensors.
Select the Manual option for FDU8x sensors.
• Detected
Only displayed if Sensor selection = Automatic
Displays the sensor type detected automatically.