Commissioning Prosonic S FMU90 PROFIBUS DP
54 Endress+Hauser
9.3.3 Parameter set "Linearization"
Purpose of linearization
To calculate the flow Q from the measured upstream level h.
Navigation
Basic setup → Linearization
Parameters
Type
"Flume/weir" option
Select this option to use a pre-programmed linearization curve.
"Table" option
Select this option to enter a linearization table of your choice.
"Formula" option
Select this option to use a flow formula: Q = C (h
α
+ γh
β
)
Flow unit
Specify the unit for the linearized value.
Curve
Only displayed if Type = Flume/weir.
Specify the shape of the flume or weir in the first step.
Then specify the size of the flume or weir in the next step.
Width
Only displayed if Type = Rectangular weir, NFX or Trapezoidal weir
Select the width of the weir.
Edit
Only displayed if Type = Table.
Opens the Edit parameter set to enter the linearization table.
Status table
Activates or deactivates the linearization table.
alpha, beta, gamma, C
Only displayed if Type = Formula.
Assign suitable values to the parameters of the flow formula.
Maximum flow
Confirm the value displayed for the maximum flow of the flume or weir or enter a
suitable value.
9.3.4 Table editor
Linearization table conditions:
Up to 32 "Level h/flow Q" value pairs.
Monotonically increasing or decreasing. (The monotonicity is checked when the
table is activated.)
Once entered, must be activated by the Status table parameter.
1
0,0000
0,0000
2
0,0000
0,0000
3
0,0000
0,0000
0,0000
0,0000
A B C
A0040751
A Line number
B Column for level
C Column for flow
1. Press to jump to the next line.
2. Press to jump to the previous line.
3. Press to open the marked line for processing.