Commissioning Prosonic S FMU90 PROFIBUS DP
52 Endress+Hauser
9 Commissioning
9.1 Preparatory steps
9.1.1 Reset to factory settings
NOTICE
A reset may negatively impact the measurement.
Perform a new basic setup after resetting the device.
Using the reset function
It is always advisable to reset the device if you want to use a device with an unknown
history.
Effects of a reset
All the parameters are reset to the factory setting.
Linearization is disabled. If a linearization table is present it is not deleted, however, and
can be reactivated if necessary.
Interference echo suppression (mapping) is disabled. The mapping curve is not deleted,
however, and can be reactivated if necessary.
Effect on a 5-point linearization protocol
With the creation of a 5-point linearity protocol, the measuring system (FDU9x sensor and
FMU9x transmitter) is adjusted and the measuring accuracy is optimized for the specified
range.
The Zero distance service parameter is fine-adjusted for this adjustment. Following a
reset, this parameter must be re-configured in the Service menu according to the data
indicated on the 5-point linearity protocol for the FDU9x sensor. Please contact Endress
+Hauser customer service for this purpose.
Performing a reset
1. Navigate to Device properties → Password/reset → Reset.
2. Enter "33333".
9.2 Switching on the measuring device
Parameters that need to be configured when the device is switched on for the first
time
Language
Select the language of the display.
Length unit
Select the unit of length in which the distance is measured.
Temperature unit
Select the unit for the sensor temperature.
Operating mode
The possible options depend on the device version and installation environment.
Controls
Choose whether pump control or rake control should be configured.